Guangdong Air Giant Fire Equipment Co.,Ltd.

Service is the base; good quality is the way of long-term development; innovation is the way to keep alive.

Manufacturer from China
Verified Supplier
3 Years
Home / Products / FM200 Fire Suppression System /

Hanging FM200 Fire Extinguishing System Without Residue For UPS Room

Contact Now
Guangdong Air Giant Fire Equipment Co.,Ltd.
Visit Website
City:guangzhou
Country/Region:china
Contact Person:MrMissaya Lu
Contact Now

Hanging FM200 Fire Extinguishing System Without Residue For UPS Room

Ask Latest Price
Video Channel
Brand Name :Air Giant
Model Number :XQQC16/1.6, XQQC20/1.6, XQQC30/1.6
Certification :CAL,CMA,CNAS,ILAC-MRA,CCC
Place of Origin :China
MOQ :1 set
Price :negotiation
Payment Terms :L/C , D/P, T/T, Western Union, Paypal, Credit card
Supply Ability :28000 sets per week
Delivery Time :10-15 working days
Packaging Details :Plywood outer box with bubble bag or paper
Cylinder Volume :16L, 20L, 30L
Pattern of extinguishing :Enclosed flooding
Agent :HFC-227ea(FM200)
Working pressure :1.6MPa
Color :Red
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Hanging FM200 Fire Extinguishing System Without Residue For UPS Room

Hanging type FM-200 fire extinguisher is a preset and independent fire extinguishing system. It is easily wall or ceiling mounted in the protected area to directly put out the fire, without pipe network distribution.

The electromagnetic actuated hanging extinguisher has two activation methods. When control panel receives signal from smoke/heat detector of fire alarm, it will send signal to electromagnetic extinguisher automatically which opens container valve, so to discharge fire extinguishing agent. It also could be activated by manual control button.

Another version:

Hanging type FM-200 fire extinguisher

Preset and independent
It is easily wall or ceiling mounted in the protected area to directly put out the fire, without pipe network distribution.
It has two activation methods: automatically send the signal to control panel for releasing the agent by electricity and manual control mode.

Parameters

No Specifications Parameters
1 Tank size 16Ltr, 20Ltr, 30Ltr
2 Device model XQQC16/1.6, XQQC20/1.6, XQQC30/1.6
3 Storage pressure 1.6MPa
4 Maximum working pressure 2.5MPa
5 Discharge time ≤8s
6 Maximum filling rate 1kg/L
7 Device starting power DC24V/1.6A
8 Environment temperature of protection zone 0℃~50℃

Below data refers to regular temperature at 20 centigrade and atmospheric pressure at 1 bar. The max coverage would vary a little from the ambient temperature and pressure on the real condition.

Device model Filling amount (kg) Maximum working pressure(Mpa) Storage pressure (Mpa) Maximum coverage
(m³)
Starting mode
XQQC16/1.6 16 2.5 1.6 22.22

Starting power:
DC24V/1.6A

Solenoid actuator

XQQC20/1.6 20 2.5 1.6 27.78
XQQC30/1.6 30 2.5 1.6 41.67

Components

One spherical pressure tank, fire extinguishing agent(HFC-227ea, same as FM200), hanging mounting, thermal sensor(one little glass tube filled with liquid whose volume will be changed by temperature), pressure switch, stainless steel pipe and nozzle.

Hanging FM200 Fire Extinguishing System Without Residue For UPS Room

Packages

We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.

Hanging FM200 Fire Extinguishing System Without Residue For UPS Room

Inquiry Cart 0